Check gas valve and central heating system pressure
Does burner light 1st
attempt?
Does burner light within 3
ignition attempts?
No
Yes
Check gas supply
Does burner light?
Yes
Check burner pressure
settings are correct
Yes
No Reset boiler
No
Check/replace gas valve
as necessary
Does burner light?
No
Replace electronic board
Yes
Is burner indicator
illuminated?
No
Check flame
rectification lead and
electrode
Is burner indicator
illuminated
No
Yes
Does burner shut down after
approx. 15 secs.
No Go to sheet F
Yes
Does status code (see page 52)
show S. 53?
Check water pressure in
central heating system, refill
and vent. as necessary
Check pump is running?
Yes
Yes Replace pump
No
Is 230 VAC present at the
pump plug connection?
No
Replace electronic board
Sheet E
FAULT FINDING

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant TURBOmax Plus SERIES and is the answer not in the manual?

Vaillant TURBOmax Plus SERIES Specifications

General IconGeneral
CategoryBoiler
ModulationYes
ModelTURBOmax Plus SERIES
Fuel typeNatural gas
MountingWall-mounted
Heating CircuitSingle
Output24kW, 28kW
Warranty2 years (extendable)

Related product manuals