User's Guide _______________________________________________________________________
64 ___________________________________________________________________ M211399EN-F
Reset Transmitter
Use the RESET command to reset the transmitter.
RESET<cr>
Example:
>reset
Resetting
HMW93 / 1.00.00.0000 / XM90
>
Set BACnet Parameters
Use the BACNET command to show or set some of the transmitter’s
BACnet parameters. You can also use the BACNET command to
reinitialize the BACnet stack of the transmitter without having to reset or
power cycle the transmitter.
BACNET [parameter_name [parameter_value]] [reinit]<cr>
where
parameter_name
=
Name of the BACnet parameter to change. Available
parameters are:
Instance
: BACnet instance number. Unsigned
(0
... 4194302).
Name
: BACnet Object_Name shown in the Device
object. String, no spaces.
Description
: BACnet Description shown in the
Device object. String, no spaces.
Location
: BACnet Location shown in the Device
object. String, no spaces.
Password
: Password used in ReinitializeDevice
service. String, no spaces.
MAX_MASTER
:
Max_Master parameter in Device
object. Unsigned (0
... 127)
parameter_value
=
New value of the parameter. See descriptions above
for allowed values.
reinit
=
Reinitializes the BACnet stack. Must be given as the
only argument for the BACNET command.