Appendix A _________________________________________________________ BACnet Reference
VAISALA ________________________________________________________________________ 91
(Application Type)
(Conforma
BACnetObjectIdentifier
AI2 (Relative Humidity)
AI3 (Temperature)
AI4 (Dewpoint)
AI5 (Dewpoint (Tdf))
AI6 (Dewpoint
depression)
AI7 (Wet bulb
temperature)
AI8 (Absolute humidity)
AI9 (Mixing ratio)
AI10 (Enthalpy)
AV1 (Pressure)
BACnetSegmentation
(ENUMERATED)
ding
BACnetAddressBindin
Object_Identifier
Must be unique in BACnet network. As Object Identifier is 22 bits long
its value range is 0 ... 4194303. Each device is assigned a random value
in this range at Vaisala factory.
Object_Name
Must be unique in BACnet network. Default object name contains the
name and serial number of the device. For example:
- Device model is HMW95, with serial number G1234567.
- Object_Name is "HMW95_G1234567".
System_Status
System status can be OPERATIONAL (0) or NON-OPERATIONAL (4).
Device goes to NON-OPERATIONAL state in case of fatal error.