EasyManua.ls Logo

Vaisala Indigo200 - Figure 21 Relay Settings Example: One Setpoint Without Hysteresis

Vaisala Indigo200
58 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 21 Relay settings example: one setpoint without hysteresis
To define a single setpoint for relay activation when the measurement exceeds the defined
activation limit (Activate above) without using hysteresis:
1. Select to access Insight main menu.
2. In the Configure Device menu, select either relay A or relay B.
3. Enable the relay output by setting Relay output on/o to ON.
4. Select the measurement parameter that is used to control the relay with the Output
parameter dropdown.
The parameter options depend on the connected probe. Note that the parameter units are
defined in the Settings menu: see Unit settings (page 26).
5. Enter the activation limit value in the Activate above field.
With this configuration, there is no hysteresis buer. The relay activates or
switches o immediately after passing this point.
6. Leave the Activate below field empty and set the Hysteresis field value as 0 (no
hysteresis).
7. Select the Error output state for the relay.
8. Select Save to store the configuration.
Chapter 6 – Configuring relays
37

Table of Contents

Related product manuals