9. Select Save to store the configuration.
With this configuration, the relay activates when measurement falls below the value
entered in the Activate below field (100 ppm in this example). When the measurement
returns above the Activate below limit, the relay does not switch o until it has reached
the combined value of the activation limit and hysteresis buer (120 ppm in this example).
For further examples on the eect of hysteresis, see Figure 20 (page 36).
Chapter 6 – Configuring relays
39