Chapter 7 ___________________________________________________ Retrieving Data Messages
VAISALA______________________________________________________________________ 111
Command format: aRx!
The response:
a+<data fields><cr><lf>
NOTE
For using Continuous measurement commands for all WXT530 series
parameters (wind, PTU, precipitation, and supervisor) the select the
respective protocol (aXU,M=R).
The M=S selection requires use of aM, aMC, aC, aCC + aD
commands, only the precipitation data can be retrieved continuously
(using aR3 command).
where
a = Device address
R = Start continuous measurement command:
x = The desired sensor to make the measurement:
1 = Wind
2 = Temperature, humidity, pressure
3 = Precipitation
5 = Supervisor
If x is left out, the query refers to the combined data
message used for requesting data from several
sensors with just one command.
! = Command terminator
where
a = Device address
<data
fields>
= The measured parameters in selected units, separated
with '+' marks (or '-' marks in case of negative
parameter values). The maximum number of
parameters to be measured with one request is 15.
<cr><lf> = Response terminator