4.2. Auxiliary voltage
The external auxiliary voltage Uaux (standard 40 to 265 V
ac/dc or 24 V dc, option B) for the relay is connected to the
terminals X1: 11 - 12
Note:
Polarity of the auxiliary voltage U
aux
(24 V dc, option B):
+ = X1:11 and - = X1:12.
4.3. Output relays
The VAMP 150 relay is equipped with five configurable output
relays and a separate output relay for the self-supervision
system
Trip relays T1 and T2 (terminals X2: 19 - 20 and 16 - 17)
Alarm relays A1 - A3 (terminals X2: 13 - 14, 11 - 12 and 9 -
10)
Self-supervision system output relay IF (terminals X2: 7 - 8)
The trip relay T2 can also be used for alarm purposes.
4.4. Serial communication connections
RS 232 serial communication connection for computers,
connector LOCAL (RS 232), connector on the front panel of
the relay
Remote control connection, connector REMOTE (TTL) on
the rear panel of the relay (terminal X5). See also Table
2.5.2-1.
4.5. Current transducer
The output signal, i.e. 0 - 20 mA or 4 - 20 mA, of the integrated
mA transducer is available on terminal X2: 1 - 2.
Available couplings to the analog output
I
L1
, I
L2
, I
L3
, I
L
I
0
f
I2/I1
I
Fault