5.7 Auto-reclose function (79) 5 Control functions Technical description
164
VAMP 24h support phone +358 (0)20 753 3264 VM50.EN004
Measured and recorded values of AR function:
Parameter Value Unit Description
Obj1 UNDEFINED;
OPEN;
CLOSE;
OPEN_REQUEST;
CLOSE_REQUEST;
READY;
NOT_READY;
INFO_NOT_AVAILABLE;
FAIL
-
Object 1
state
Status INIT;
RECLAIM_TIME;
READY;
WAIT_CB_OPEN;
WAIT_CB_CLOSE;
DISCRIMINATION_TIME;
LOCKED;
FINAL_TRIP;
CB_FAIL;
INHIBIT
-
AR-function
state
Shot# 1…5 -
The
currently
running shot
ReclT RECLAIMTIME;
STARTTIME;
DEADTIME;
DISCRIMINATIONTIME
-
The
currently
running time
(or last
executed)
SCntr -
Total start
counter
Fail -
The counter
for failed AR
shots
Shot1 * -
Shot1 start
counter
Shot2 * -
Shot2 start
counter
Shot3 * -
Shot3 start
counter
Shot4 * -
Shot4 start
counter
Measured
or
recorded
values
Shot5 * -
Shot5 start
counter
*) There are 5 counters available for each one of the two AR signals.