EasyManua.ls Logo

VAMP 52 - Page 190

Default Icon
232 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.3 Trip circuit supervision 7 Application Technical description
190
VAMP 24h support phone +358 (0)20 753 3264 VM50.EN004
The external resistance value is calculated using Equation
7.3.1-1.
Equation 7.3.1-1
DI
coilDIDI
I
RIUU
R
min
R = (88 – 18 – 0.003*242)/0.003 = 23.1 k
(In practice the coil resistance has no effect.)
By selecting the next smaller standard size we get 22 k.
The power rating for the external resistor is estimated using
Equation 7.3.1-2 and Equation 7.3.1-3. The Equation 7.3.1-2 is
for the CB open situation including a 100 % safety margin to
limit the maximum temperature of the resistor.
Equation 7.3.1-2
RIP
DI
2
2
P = 2*0.003^2x22000 = 0.40 W
Select the next bigger standard size, for example 0.5 W.
When the trip contacts are still closed and the CB is already
open, the resistor has to withstand much higher power
(Equation 7.3.1-3) for this short time.
Equation 7.3.1-3
R
U
P
2
max
P = 121^2/22000 = 0.67 W
A 0.5 W resistor will be enough for this short time peak power,
too. However, if the trip relay is closed for longer time than a
few seconds, a 1 W resistor should be used.

Table of Contents

Related product manuals