Series 612
INSTALLATION
601894EA
Edition 2013-04-12
35/83
4.6.7.1 Gain factor adjustment
The gain factor effects: Stability, Response time
Default value is 1. Adjustment range is from 0.0001 to 7.5.
Higher gain results in: faster response / higher over- / undershoot of pressure
Lower gain results in: slower response/ lower over- / undershoot of pressure
Adjustment procedure:
1. Start with gain factor 1.0
2. Open valve.
3. Control a typical pressure / flow situation.
4. Repeat from step 2 with lower (higher) gain factors until optimal pressure response is achieved and
stability is ok.
Normally adjustments down to gain factors of 0.42 should lead to good results.
Otherwise you may need to improve sensor connection. Refer to «Requirements to
sensor connection».
Local operation:
(‘Control View’, ‘Control Performance Analyzer’
or ‘Service Box 2‘)
Remote operation:
(Refer to chapter «RS232 setup commands» for
details)
Set gain factor in menu ‘Setup / Control
Parameter’
Send
PID CONTROLLER CONFIGURATION