INSTALLATION
Series 612
Edition 2013-04-12
601894EA
4.7.5 Error messages
Description
Error message
Protocol
Parity error
[E:][000001][CR][LF]
Framing error (data length, number of stop bits)
[E:][000003][CR][LF]
Input buffer overflow (to many characters)
[E:][000002][CR][LF]
Commands
<CR> or <LF> missing
[E:][000010][CR][LF]
: missing
[E:][000011][CR][LF]
Unknown command
[E:][000020][CR][LF]
[E:][000021][CR][LF]
Invalid value
[E:][000022][CR][LF]
[E:][000023][CR][LF]
Value out of range
[E:][000030][CR][LF]
Invalid number of characters (between : and [CR][LF])
[E:][000012][CR][LF]
Setup
ZERO disabled
[E:][000060][CR][LF]
Device Status
Command not accepted due to local operation
[E:][000080][CR][LF]
Command not accepted due to synchronization, CLOSED or OPEN by digital input,
safety mode or fatal error
[E:][000082][CR][LF]
Hardware
Command not applicable for hardware configuration
[E:][000041][CR][LF]

Table of Contents