data length 8 characters
a 0 (reserved, do not change)
b gain factor:
0 = 0.10, 1 = 0.13, 2 = 0.18, 3 = 0.23, 4 = 0.32, 5 = 0.42, 6 = 0.56
7 = 0.75, 8 = 1.00, 9 = 1.33, A = 1.78, B = 2.37, C = 3.16, D = 4.22
E = 5.62, F = 7.50, G = 0.0001, H = 0.0003, I = 0.001, J = 0.003,
K = 0.01, L = 0.02, M = 0.05
c sensor delay:
0 = 0.00, 1 = 0.02, 2 = 0.04, 3 = 0.06, 4 = 0.08, 5 = 0.10, 6 = 0.15,
7 = 0.20, 8 = 0.25, 9 = 0.30, A = 0.35, B = 0.4, C = 0.50, D = 0.60,
E = 0.80, F = 1.00
d setpoint ramp:
0 = 0.0, 1 = 0.5, 2 = 1.0, 3 = 1.5, 4 = 2.0, 5 = 2.5, 6 = 3.0, 7 = 3.5,
8 = 4.0 , 9 = 4.5, A = 5.0, B = 5.5, C = 6.0, D = 6.5, E = 7.0, F = 7.5,
G = 8.0, H = 8.5, I = 9.0, J = 9.5, K = 10.0
efgh 0000 (reserved, do not change)
This command selects gain factor, sensor response time and setpoint ramp for the PID
controller.
Note: Refer to «Tuning of control performance» for details.
data length 6 characters starting with double zero for writing
8 characters starting with quadruple zero for reading
xxxx valve speed, 1 ... 1000 (1 = min. speed, 1000 = max. speed)
This command allows changing the actuating speed of the valve plate. Speed selection is
effective for pressure control and position control. Open valve and close valve are always
done with max. speed.
Note: Refer to «Valve speed adjustment» for details.