3.11.8.2 Details 
 
The commands are in view from valve to the customer CC-Link-Net. 
 
Signal 
Type 
Name 
Start 
Word
Byte 
Length 
Data 
Type 
Valid 
Range 
Description 
Signal 
PRESSURE 
0 4 
signed 
integer 
(default) or 
floating point
-270000.. 
1’230’000 
(default) 
(-2.7V..12.3V 
sensor signal), 
adjustable
1)
 
In case of default valid range: 
Physical full scale value of the sensor 
(10 Volt) equals to 1’000’000. 
(In case of 2 sensor operation the full 
scale of high range sensor equals to 
1’000’000.) 
Signal 
PRESSURE SENSOR 1 
2 4 
signed 
integer 
(default) or 
floating point
-270000.. 
1’230’000 
(default) 
(-2.7V..12.3V 
sensor signal), 
adjustable
1)
 
In case of default valid range: 
Physical full scale value of the sensor 
(10 Volt) equals to 1’000’000. 
Signal 
PRESSURE SENSOR 2 
4 4 
signed 
integer 
(default) or 
floating point
-270000.. 
1’230’000 
(default) 
(-2.7V..12.3V 
sensor signal), 
adjustable
1)
 
Optional, only in case of 2 sensor 
version. 
In case of default valid range: 
Physical full scale value of the sensor 
(10 Volt) equals to 1’000’000. 
Signal  POSITION  6 4 
signed 
integer 
(default) or 
floating point
0..100’000 
(default),  
adjustable
1)
 
min signal value  = “valve is closed” 
max signal value = “valve is opened” 
 
The position 9’999’999 (or 9’999’999.0 
for floating point) show an unknown 
valve position – e.g. during 
synchronization at startup 
Signal 
CONTROL MODE 
10 1 
unsigned 
integer 
0…14 
0 = init 
1 = synch 
2 = position 
3 = close 
4 = open 
5 = pressure 
6 = hold 
7 = learn 
8 = interlock open 
9 = interlock close 
10 = maintenance open 
11 = maintenance close 
12 = power failure 
13 = safety 
14 = fatal error