Installation, Operating & Maintenance Instructions
Series 650 DN 100-250 (I.D. 4“ - 10”), CC-Link
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
280672EB
2010-12-15
67/94
Signal
Type
Name
Start
Word
Byte
Length
Data
Type
Valid
Range
Description
Signal FATAL ERROR 11 1
unsigned
integer
20,21,22,25,40
20 = no stop detected during synch
mode
21 = valve blocked during synch mode
22 = valve blocked
25 = step loss during synch mode
40 = motor driver fault
Bitmap
GENERAL STATUS
16 2
boolean
array
See bitmap table below
Bitmap
GENERAL WARNING
17 2
boolean
array
See bitmap table below
Bitmap
EXTENDED WARNING
18 2
boolean
array
See bitmap table below
Signal
CLUSTER VALVE
MONITORING
ADDRESS
19 1
unsigned
integer
0…254
Actual address of the selected cluster
valve.
Signal
CLUSTER VALVE
POSITION
20 4
signed
integer
(default) or
floating point
0…100’000
(default),
adjustable
1)
Actual position of the selected cluster
valve.
Signal
CLUSTER VALVE
CONTROL MODE
22 1
unsigned
integer
0…14
0 = init
1 = synch
2 = position
3 = close
4 = open
5 = pressure
6 = hold
7 = learn
8 = interlock open
9 = interlock close
10 = maintenance open
11 = maintenance close
12 = power failure
13 = safety
14 = fatal error
Bitmap
CLUSTER VALVE
STATUS
23 1
boolean
array
See bitmap table below
Bitmap
CLUSTER VALVE
WARNINGS
24 1
boolean
array
See bitmap table below
1) To adjust range refer to chapter: «Range of pressure and position values»