4 Mounting
VEGAPULS 63 • Modbus and Levelmaster protocol
41364-EN-170711
Fig.8:Mountingoftheradarsensorwithinowingmedium
Flush mounting
The best way to mount the sensor, also with respect to cleanability,
isushonablockange(angewithoutsocketpiece)orthrougha
hygienictting.
Mounting on socket
Ifthereectivepropertiesofthemediumaregood,youcanmount
VEGAPULS63onasocketpiece.Youwillndrecommendedvalues
for socket heights in the following illustration. The socket end should
be smooth and burr-free, if possible also rounded. Then carry out a
false signal suppression.
d
h
max.
Fig. 9: Deviating socket dimensions
The below charts specify the max. socket length h depending on the
diameter d.
Socket diameter d Socket length h
50 mm ≤100mm
80 mm ≤300mm
100 mm ≤400mm
Mounting socket