92
12 Menu overview
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66190-EN-221107
Access protection
Menu item Parameter Selection Default setting
Access protection Bluetooth access
code
Bluetooth access code
Protection of the pa-
rameterization
Protection of the parameterization
Device code Device code
Reset
Menu item Parameter Selection Default setting
Reset Reset Reset to factory settings, Restart -
Extended settings
Menu item Parameter Selection Default setting
Temperature unit °C, °F, K °C
Damping Integration time 0 … 999 s 0 s
Current output Output value Percent,linearizedpercent,llingheight,
distance, scaled, measurement reliability,
electronics temperature, meas. rate, sup-
ply voltage
Percent
Output character-
istics
0 … 100 % correspond to 4 … 20 mA 0 … 100 % corre-
spond to 4 … 20 mA
0 … 100 % correspond to 20 … 4 mA
Current range 4 … 20 mA 4 … 20 mA
3.8 … 20.5 mA
Reaction when mal-
functions occur
≤3.6mA,≥21mA,lastvalidmeasured
value
≤3.6mA
Linearisation Linearization type -
liquid
Linear, cylindrical tank, spherical tank,
Venturi, trapezoidal weir, rectangular weir,
Palmer-Bowlusume,V-Notch,triangu-
lar overfall
Linear
Linearization type -
bulk solids
Linear, conical bottom, pyramid bottom,
sloping bottom
Linear
Intermediate height
"h"
Scaling Scaling size Scaling size (dimensionless, mass, volume,
height,pressure,ow,others)
Dimensionless
Scaling unit (unit selection depending on
scalingsize,user-dened)
-
Scaling format #, #.#, #.##, #.###, #.#### #
Scaling Scaling 100 % correspond to
0 % correspond to