LINE SIZE & PRESSURE RATINGS
REV : 18
REV : 08/2024
DPN000788
Page :1/4
DPN001040_REV6
AIR-COOLED SYSTEMS USING R-410A
Notes:
1. Consult factory for proper line sizing for runs longer than maximum equivalent length shown in table.
2. Must downsize vertical riser one trade size (1-1/8” to 7/8” or 7/8” to 3/4” or 3/4" to 5/8" or 5/8" to 1/2").
3. Consult factory when actual pipe length between Liebert® MC/Liebert® EconoPhase and Liebert® DSE unit will exceed 300 ft (91 m).
4. Liebert® DSE DA250-265 and Vertiv® CoolPhase CDU XDM300 units can be extended to max 200ft (61m) linear or 300ft. (91m) equivalent.
5. Consult factory for Vertiv® CoolPhase CDU modules where pipe lengths exceed 300 ft (91m), or where oversized piping is considered,
such as a Vertiv® CoolPhase CDU that replaces existing Liebert® DSE DA250 models and/or uses existing piping.
Indoor Model Equivalent Length 50 ft (15m) 75 ft (23m) 100 ft (30m) 125 ft (38m) 150 ft (45m)
Suction Line, in. 7/8 7/8 7/8 7/8 7/8
Liquid Line, in. 1/2 1/2 1/2 1/2 1/2
Suction Line, in. 7/8
1-1/8
2
1-1/8
2
1-1/8
2
1-1/8
2
Liquid Line, in. 1/2 1/2 5/8 5/8 5/8
Suction Line, in. 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8
Liquid Line, in. 1/2 5/8 5/8 5/8 5/8
Product
Variable Capacity
Digital Scroll Models
MT060
MT048
MT036
RECOMMENDED REFRIGERANT LINE SIZES CU, OD
PRODUCT Indoor Model
50 ft (15m)
300 ft (91m)
Hot Gas Line, in. 3/4 3/4 3/4
Liquid Line, in. 5/8 5/8 5/8 3/4
Hot Gas Line, in. 7/8 7/8 7/8
Liquid Line, in. 3/4
Hot Gas Line, in. 1/2 5/8 5/8 5/8
Liquid Line, in. 3/8 1/2 1/2 1/2
Hot Gas Line, in. 5/8 5/8 5/8
Liquid Line, in. 1/2 1/2 1/2 5/8
Hot Gas Line, in. 3/4 3/4 3/4
Liquid Line, in. 5/8 5/8 5/8 5/8
Hot Gas Line, in. 7/8 7/8 7/8
Liquid Line, in. 5/8 5/8 5/8 3/4
Hot Gas Line, in. 1-1/8 1-1/8 1-1/8 1-1/8
Liquid Line, in. 7/8 7/8 7/8 7/8
Hot Gas Line, in. 1-3/8 1-3/8 1-3/8 1-3/8
Liquid Line, in. 7/8 7/8 7/8 7/8
Hot Gas Line, in. 1-3/8 1-3/8 1-3/8 1-3/8
Liquid Line, in. 7/8 1-1/8 1-1/8 1-1/8
Hot Gas Line, in. 1-3/8 1-3/8 1-3/8 1-3/8
Liquid Line, in. 7/8 1-1/8 1-1/8 1-1/8
Hot Gas Line, in. 1-5/8 1-5/8
Liquid Line, in. 1-3/8 1-3/8
Hot Gas Line, in. 1-3/8 1-3/8 1-3/8 1-3/8
Liquid Line, in. 7/8 1-1/8 1-1/8 1-1/8
Hot Gas Line, in. 1-5/8 1-5/8
Liquid Line, in. 1-3/8 1-3/8
XDM 200
XDM 300
Vertiv™ CoolPhase
CDU
Liebert® XDM
Any Compressor Type
CR019RA/ CR020RA
DA125
DA150
PX011
Liebert® CRV
Liebert® PDX
Liebert® DSE
DA165
CR035RA
PX018
PX023
PX029
DA050 / DA080/
DA085
DA250 / DA265