High Side Low Side High Side Low Side High Side Low Side
Design Pressure N/A N/A 511 (3523) 235 (1620) N/A N/A
High Pressure Cutout N/A N/A 561 (3868) N/A N/A N/A
Design Pressure 364 (2510) 165 (1138) N/A N/A N/A N/A
High Pressure Cutout 400 (2758) N/A N/A N/A N/A N/A
Design Pressure N/A N/A 530 (3655) 235 (1620) 500 (3447) 215 (1482)
High Pressure Cutout N/A N/A 580 (3999) N/A 540 (3723) N/A
Design Pressure N/A N/A 530 (3655) N/A N/A N/A
High Pressure Cutout N/A N/A N/A N/A N/A N/A
Design Pressure 364 (2510) 530 (3655) N/A N/A
High Pressure Cutout N/A N/A N/A N/A N/A N/A
Design Pressure N/A N/A 530 (3655) N/A N/A N/A
High Pressure Cutout N/A N/A N/A N/A N/A N/A
Design Pressure N/A N/A 530 (3655) 235 (1620) N/A N/A
High Pressure Cutout N/A N/A 580 (3999) N/A N/A N/A
Design Pressure 315 (2172) 165 (1138) N/A N/A N/A N/A
High Pressure Cutout 400 (2758) N/A N/A N/A N/A N/A
Design Pressure N/A N/A 530 (3655) 235 (1620) N/A N/A
High Pressure Cutout N/A N/A 580 (3999) N/A N/A N/A
Design Pressure 320 (2206) N/A N/A N/A N/A N/A
High Pressure Cutout N/A N/A N/A N/A N/A N/A
Design Pressure 300 ( 2068) 475 (3275) N/A N/A
High Pressure Cutout N/A N/A N/A N/A N/A N/A
Design Pressure N/A N/A 530 (3655) 235 (1620) N/A N/A
High Pressure Cutout N/A N/A 580 (3999) N/A N/A N/A
Design Pressure N/A N/A 530 (3655) 235 (1620) N/A N/A
High Pressure Cutout N/A N/A 580 (3999) N/A N/A N/A
Design Pressure 364 (2510) 163 (1124) N/A N/A N/A N/A
High Pressure Cutout 400 (2758) N/A N/A N/A N/A N/A
Liebert® Fin/Tube Condenser
System Fluid : R-407C
psig (kPa)
System Fluid : R-410A
psig (kPa)
Liebert® CRV
2
Liebert® DS
2
Liebert® DSE (DA050-DA265)
Liebert® EconoPhase
Product Pressure Type
System Fluid : R-454B
psig (kPa)
Liebert® Piggyback (Condenser)
Liebert® DSE (DP060, DP400, DP500)
Vertiv
™
CoolPhase CDU & Liebert®
XDM
Liebert® XDC
Liebert® MC Condenser
Liebert® MCV
3
Liebert® PDX
2
Liebert® Mini-Mate Variable Capacity
(PFD, MT, MTC)
2
Liebert® Mini-Mate2 (PFH, MCD)u
Liebert® Datamate (DME, DMC)
2
LINE SIZE & PRESSURE RATINGS
REV : 18
REV : 08/2024
DPN000788
Page :4/4
DPN001040_REV6
SYSTEM REFRIGERANT PRESSURES
Notes:
1. Field installed interconnecting piping must be properly selected and installed based on local and national codes, the user manual, and the unit serial tag.
2. Values apply to air cooled and fluid cooled systems.
3. Product is a Heat Rejection packaged condenser. For more information see product manual.
4. Design Pressure is noted on the serial tag in all above product lines.
5. High Pressure Cutout is nominal in all above product lines.