Model Voltage FLA WSA OPD
MCV440 + PR250*****5
2 = 380V/60Hz 35.8 36.8 40
A = 460V/60Hz 28.8 29.6 30
G = 415V/50Hz N/A N/A N/A
B = 575V/60Hz 23.1 23.8 35
MCV430 + PR250
2 = 380V/60Hz 29.4 30.5 35
A = 460V/60Hz 23.8 24.7 25
G = 415V/50Hz 28.4 29.3 30
B = 575V/60Hz 19.0 19.7 30
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device.
Table 6.2 Heat Rejection Skid Electrical Data, Three-Phase (continued)
Model Voltage FLA WSA OPD
MCV440
2 = 380V/60Hz 28.0 28.9 30
A = 460V/60Hz 22.4 23.1 25
M = 380-415V/50Hz 28.0 28.9 30
G = 415V/50Hz 28.0 28.9 30
MCV430
2 = 380V/60Hz 21.0 21.9 25
A = 460V/60Hz 16.8 17.5 20
M = 380-415V/50Hz 21.0 21.9 25
G = 415V/50Hz 21.0 21.9 25
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device.
Table 6.3 Vertiv™ Liebert® MCV Condenser Only Electrical Data, Three-Phase
60 Proprietary and Confidential ©2024 Vertiv Group Corp. 6 Heat Rejection Skid
Vertiv™ CoolPhase CDU Installer/User Guide