Figure 3.38 SYS Parameter Screen 2
1. Float VOL: The setting point of battery float voltage. 13.6V is default setting.
2. UPS Type: There are two options, HV and LV. This change is only allowed for qualified technician.
NOTE: It is required to restart the UPS after setting.
3. Power Setting: Set power factor in percentage.
4. Output setting: Set UPS output setting. There are two selections, 3-1 (it is available only for 10-15-20kVA) and 3-
3.
NOTE: It is required to restart the UPS after setting.
5. Customer Code: Set customer code. It is a necessary setting when using dynamic password function.
6. Dynamic Password: Enable or disable dynamic password function.
52 Proprietary and Confidential ©2024 Vertiv Group Corp. 3 Operations
Vertiv™ Liebert® MTP Online UPS User Manual 20-40-80kVA