MENU
NAME
DATA ITEM DATA DESCRIPTION
Battery
Batt Voltage (V) Battery bus voltage
Batt Current (A) Battery bus current
Runtime (Min.) Battery backup time remaining
Batt Capacity
(%)
Percentage of battery capacity
Batt State Charging, discharging or fully charged
Batt String
Count
Online battery string count
Batt Temp (°C) Battery temperature
Discharge
Count
Maximum historical discharge count within current battery modules
Discharge Time
(H)
Maximum historical discharge time within current battery modules
EBC Count Number of connected External Battery Cabinets
Output
L-N Voltage (V) L-N Output Voltage
L-N Current (A) L-N Output Current
Frequency (Hz) Output Frequency
Power Factor Output Power Factor
Line Voltage (V) L-L Output Voltage (not displayed for single-phase output model)
Load
kVA Output apparent power
kW Output active power
Load Level (%) Output loading, indicated in percentage of the UPS system rated load
Crest Factor Output current peak value factor
UPS Info
UPS ID UPS ID
LCD Module If the module is online, the serial number and software version will be displayed
Bypass Monitor
Module
If the module is online, the serial number and software version will be displayed
Bypass Control
Module
If the module is online, the serial number and software version will be displayed
Charger Module If the module is online, the serial number and software version will be displayed
Power Module If the module is online, the serial number and software version will be displayed
Battery Module If the module is online, the serial number and software version will be displayed
Redundant
State
PM Installed The number of installed power modules
PM Whether there are redundant power modules supplying power.
Table 5.5 Item description of menu window and data window (continued)
Vertiv | Liebert® APS™ Installer/User Guide | 61