EasyManua.ls Logo

Viessmann B1HF - Checking the Gas Type; Converting the Gas Type for Operation with LPG

Viessmann B1HF
116 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38
Activating the venting function
If the venting function is to be activated after commis-
sioning.
Tap the following buttons:
1. and OK simultaneously for approx. 4 s, then
release.
2. Use / to select "b.5" for the commissioning
assistant.
3. OK
4. The display shows "AP".
Press for 4 s.
5. Use / to select "C.2" for ventilation.
6. OK
7. / should be used to select "ON" to switch on
the ventilation.
8. OK
The venting function is activated. The display
shows a circulating rectangle.
The venting function ends automatically after
20 min, or press for 4 s.
Checking the gas type
The boiler is equipped with an electronic combustion
controller that adjusts the burner for optimum combus-
tion in accordance with the prevailing gas quality.
For operation with natural gas, no adjustment is
therefore required across the entire Wobbe index
range. The boiler can be operated within the Wobbe
index range 9.5 to 15.2 kWh/m
3
(34.2 to
54.7 MJ/m
3
).
For operation with LPG, the gas type needs to be
changed on the control unit (see following chapter).
1. Determine the gas type and Wobbe index by ask-
ing your local gas supply utility or LPG supplier.
2. Record the gas type in the service report.
Converting the gas type for operation with LPG
1. To change the gas type on the control unit, see
"Commissioning the system with the commission-
ing assistant"
Note
No mechanical adjustments are made to the gas
solenoid valve.
2. Affix label "G31" (supplied with the technical docu-
mentation) adjacent to the type plate on the cover
panel.
Commissioning, inspection, maintenance
Venting the heating system (cont.)
6167586

Table of Contents

Related product manuals