Displayed fault
code
System characteristics Cause Measures
345 Burner locked out, automatic
enabling after appliance cool-
down. Independent restart
Temperature limiter has
responded.
Ensure adequate heat transfer.
Check heating system fill level.
Check pre-charge pressure in di-
aphragm expansion vessel. Ad-
just to required system pressure.
Check whether flow rate is suffi-
cient (circulation pump).
Check function of 3-way diverter
valve. Vent the system.
If the fault occurs during DHW
heating: Check DHW cylinder or
plate heat exchanger for contami-
nation and scaling.
346 Burner in a fault state Ionisation current calibra-
tion error
Check the gas supply pressure.
Check gas solenoid valve strain-
er on the inlet side for contami-
nation.
Check ionisation electrode for
contamination.
Check flue system. Remove flue
gas recirculation if required.
Check the condensate drain
(condensate blockage).
Reset the appliance.
348 Burner in a fault state Gas modulation valve If several heat generators are con-
nected to a common flue system:
Check whether "Multiple connec-
tions" is set in the commissioning
assistant.
Check the flue system for unre-
stricted flow.
If fault remains, replace gas fan
unit.
349 Burner in a fault state Air mass rate flow not de-
tected correctly in fan unit.
Check for dust contamination in
the supply air.
Check burner gauze assembly
for contamination.
Reset the appliance. If the fault oc-
curs repeatedly, replace the gas
fan unit.
350, 351 Burner in a fault state Ionisation current lies out-
side the permissible range
Replace the HBMU heat manage-
ment unit. See chapter "Replacing
the HBMU heat management unit".
352 Burner in a fault state Combustion CO limit ex-
ceeded
Check entire flue gas path for the
following:
Leaks
Flue gas back pressure caused
by water pocket (if flue system
fall is insufficient)
Constrictions
Blockages
Repair flue system if necessary.
Reset the appliance.
Troubleshooting
Fault messages (cont.)
6167586
Diagnosis