EasyManua.ls Logo

Viessmann VITOCAL Series - Safety valve; Automatic thermostatic mixing valve

Viessmann VITOCAL Series
152 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Vitocal 222-A
N
O
M
L
H
K
P
O
K R S K N P
K
C
B
A
G
D
E
F
A
Expansion vessel, suitable for drinking water
B
Visible discharge pipe outlet point (tundish)
C
Safety valve
D
DHW circulation pump
E
Spring-loaded check valve
F
Automatic thermostatic mixing valve
G
DHW
H
Heat pump terminal area (plan view)
K
Shut-off valve
L
Flow regulating valve
M
Pressure gauge connection
N
Non-return valve/pipe separator
O
Drain valve
P
Cold water
R
Drinking water filter
S
Pressure reducer DIN 1988-200:2012-05
Safety valve
The DHW cylinder must have a safety valve to protect against
unduly high pressure.
Recommendation: Install safety valve above top edge of cylinder.
This means the DHW cylinder will not need to be drained when
working on the safety valve.
CH: According to W3 "Principles for creating potable water installa-
tions", safety valves must be drained directly via a visible unrestric-
ted drain or via a short outlet line to the drain network.
Automatic thermostatic mixing valve
With appliances that heat DHW to temperatures above 60 °C, an
automatic thermostatic mixing valve must be installed in the DHW
line as protection against scalding.
This also particularly applies when connecting solar thermal sys-
tems.
7.12 DHW cylinder selection
When selecting the DHW cylinder ensure that its indirect coil surface
area is large enough for the purpose.
Approximate calculation of the coil surface area:
Minimum indirect coil surface area in m
2
≈ heat pump output in
kW x 0.3 m
2
/kW
Max. cylinder storage temperature
Vitocal 200-A: 50 °C
Note
The stated cylinder storage temperature can only be achieved in
the temperature range within the application limits to EN 14511 in
which the heat pump reaches the max. flow temperature.
The cylinder sizes listed in the following table are standard val-
ues. They are based on the following DHW demand: 50 l per per-
son per day at a DHW temperature of 45 °C
Design information
(cont.)