Specification
Lead length 3.0 m, fully wired
IP rating IP 32 to EN 60529; ensure through de-
sign/installation
Permissible ambient temperature
– Operation 0 to +40 °C
– Storage and transport −20 to +65 °C
9.8 Swimming pool temperature control
Temperature controller for regulating the swimming pool temperature
Part no. 7009432
Specification
Connection 3-core lead with a cross-section of
1.5 mm
2
Setting range 0 to 35 °C
Switching differential 0.3 K
Breaking capacity 10(2) A, 250 V~
Switching function with rising temperature from 2 to 3
Stainless steel sensor well R ½ x 200 mm
9.9 Extension for heating circuit control unit, general
High limit safety cut-out
Part no. 7197797
Note
Only use with heat pumps that reach a flow temperature of up to
65 °C.
If an external heat generator is connected in the secondary circuit,
the high limit safety cut-out protects the heat pump refrigerant circuit
from unacceptably high temperatures.
Examples of heat generators:
■ Solar thermal systems
■ Solid fuel boilers
■ Non-modulating boilers
The high limit safety cut-out is connected to the control unit of the
external heat generator. If the heat generator exceeds the tempera-
ture, it is switched off via the high limit safety cut-out.
Specification, high limit safety cut-out
Connection 4.2 m, fully wired
Switching point 65 °C (cannot be changed)
Switching tolerance +0/–6.5 K
IP rating IP 41 to EN 60529; ensure through de-
sign/installation.
Ambient temperature Max. 50 °C
Sensor temperature Max. 90 °C
Sensor diameter 6.5 mm