2.2 Specification
Specification
230 V appliances
Type AWO-M/AWO-M-E/AWO-M-E-AC 201.A04 201.A06 201.A08 201.A10 201.A13 201.A16
Heating performance data to EN 14511 (A2/W35)
Rated heating output kW 2.61 3.11 4.04 5.01 5.92 6.47
Fan speed rpm 600 600 650 600 600 600
Power consumption kW 0.73 0.82 1.02 1.27 1.48 1.79
Coefficient of performance ε (COP) in
heating mode
3.57 3.78 3.96 3.96 4.01 3.61
Output control kW 2.00 to 4.10 2.40 to 5.50 2.80 to 7.00 4.40 to 9.60 4.80 to
10.20
5.20 to
10.70
Heating performance data to EN 14511 (A7/W35, 5 K
spread)
Rated heating output kW 3.96 4.83 5.62 7.01 7.85 8.64
Fan speed rpm 600 600 650 600 600 600
Air flow rate
m
3
/h
2250 2250 2600 4500 4500 4500
Power consumption kW 0.87 1.02 1.19 1.49 1.66 1.90
Coefficient of performance ε (COP) in
heating mode
4.56 4.72 4.71 4.69 4.72 4.54
Output control kW 2.44 to 4.18 3.00 to 6.00 3.47 to 7.54 5.48 to
12.60
6.00 to
13.70
6.42 to
14.30
Heating performance data to EN 14511 (A–7/W35)
Rated heating output kW 3.81 5.70 6.67 8.69 9.50 11.03
Power consumption kW 1.31 1.96 2.31 2.77 3.09 3.90
Coefficient of performance ε (COP) in
heating mode
2.91 2.91 2.89 3.14 3.07 2.83
Heating performance data to EN 14511 (A35/W7)
Rated cooling capacity kW 2.00 3.00 4.00 5.00 6.00 7.00
Fan speed rpm 600 600 650 900 900 900
Power consumption kW 0.80 1.20 1.40 1.90 2.30 2.70
Energy efficiency ratio EER in cooling
mode
2.40 2.60 2.90 2.70 2.65 2.60
Output control kW Up to 3.90 Up to 4.90 Up to 6.20 Up to 8.00 Up to 9.00 Up to 10.30
Heating performance data to EN 14511 (A35/W18)
Rated cooling capacity kW 4.00 5.00 6.00 7.00 8.20 9.20
Fan speed rpm 600 600 650 900 900 900
Power consumption kW 0.80 1.35 1.40 1.67 2.08 2.42
Energy efficiency ratio EER in cooling
mode
4.20 4.20 4.30 4.10 3.95 3.80
Output control kW Up to 5.00 Up to 6.00 Up to 7.00 Up to 11.00 Up to 12.50 Up to 13.90
Air intake temperature
Cooling mode (type AWO-M-E-AC only)
Min. °C 10 10 10 10 10 10
Max. °C 45 45 45 45 45 45
Heating mode
Min. °C –20 –20 –20 –20 –20 –20
Max. °C 35 35 35 35 35 35
Heating water (secondary circuit)
Minimum flow rate l/h 700 700 700 1400 1400 1400
Minimum volume in the heating system,
cannot be fitted with shut-off devices
l 50 50 50 50 50 50
Max. external pressure drop (RFH) at
minimum flow rate
mbar 705 705 705 500 500 500
kPa 70.5 70.5 70.5 50 50 50
Max. flow temperature °C 60 60 60 60 60 60
Outdoor unit electrical values
Rated voltage, compressor 1/N/PE 230 V/50 Hz
Max. operating current, compressor A 13.0 14.6 14.6 19.9 23.3 23.3
Cos φ 0.99 0.99 0.99 0.99 0.99 0.99
Starting current, compressor A 15 15 15 15 15 15
Fuse rating B16 A B16 A B16 A B25 A B25 A B25 A
IP rating IP X4 IP X4 IP X4 IP X4 IP X4 IP X4
Vitocal 200-A