For the cabling of power supply of a CPU, a green plug with Cage-
Clamp technology is deployed. The connection clamp is realized as
plug that may be clipped of
f carefully if it is still cabled.
Here wires with a cross-section of 0.08mm
2
to 2.5mm
2
may be con-
nected. You can use flexible wires without end case as well as stiff
wires.
1 Test point for 2mm test tip
2 Locking (orange) for screwdriver
3 Round opening for wires
The picture on the left side shows the cabling step by step from top
view
.
1. For cabling you push the locking vertical to the inside with a
suiting screwdriver and hold the screwdriver in this position.
2. Insert the de-isolated wire into the round opening. Y
ou may use
wires with a cross-section from 0.08mm
2
to 2.5mm
2
3. By removing the screwdriver the wire is connected safely with
the plug connector via a spring.
CageClamp technology
(green)
VIPA System 300SAssembly and installation guidelines
Cabling
HB140 | CPU | 314-6CF03 | GB | 16-43 26