Byte Bit 7 ... 0
11
n Bit 0: Parametrization error channel 3
n Bit 1: 0 (fix)
n Bit 2: 0 (fix)
n Bit 3: 0 (fix)
n Bit 4: Wire break channel 3
n Bit 5: 0 (fix)
n Bit 6: Measuring range underflow channel 3
n Bit 7: Measuring range overflow channel 3
12
n Bit 0: Parametrization error channel 4
n Bit 1: 0 (fix)
n Bit 2: 0 (fix)
n Bit 3: 0 (fix)
n Bit 4: Wire break channel 4
n Bit 5: 0 (fix)
n Bit 6: Measuring range underflow channel 4
n Bit 7: Measuring range overflow channel 4
13
n Bit 0: Parametrization error channel 5
n Bit 1: 0 (fix)
n Bit 2: 0 (fix)
n Bit 3: Short circuit channel 5
n Bit 4: Wire break channel 5
n Bit 7 ... 5: 0 (fix)
14
n Bit 0: Parametrization error channel 6
n Bit 1: 0 (fix)
n Bit 2: 0 (fix)
n Bit 3: Short circuit channel 6
n Bit 4: Wire break channel 6
n Bit 7 ... 5: 0 (fix)
6.7 Digital part
n The digital part consists of 8 input and 8 in-/output channels. Each
of these channels shows its state via a LED.
n By means of the parametrization you may assign interrupt proper-
ties to every digital input.
n Additionally you may parametrize the digital inputs as counter with
max. 100kHz.
n The output channels provide a diagnostic function, i.e. as soon as
an output is active, the concerning input is set to "1".
n At a short circuit at the load, the input is set to "0" and the error
may be recognized by evaluating the input.
n The DIO area has to be provided with external DC 24V
.
Overview
VIPA System 300S Deployment I/O periphery
Digital part
HB140 | CPU | 314-6CF03 | GB | 16-43 145