4. PROGRAMMING
46 D-305735 PowerMaster 360 Installer's Guide
Configuration Instructions
Define the devices that cannot trigger a panic alarm.
BS8243 (default) – KF-234 PG2 and KF-235 PG2.
all - All devices can trigger a panic alarm
05:CONFIRM ALARM
Define a specific time period that if 2 successive alarms occur, the second alarm will be
considered as a confirmed alarm, (see RPT CNFM ALRM below).
Options: in 30 (default)/45/60/90 minutes
A confirmed panic alarm is reported if one of the following occurs within the confirmation time:
a) A second panic device is activated.
b) A second panic alarm on the same device is activated.
c) A tamper event is activated (not from the zone / device that initiated the panic alarm).
Options:
Define whether the system will report a confirmed alarm.
enable + bypass (default) -
The system will report a confirmed alarm and will bypass all
alarmed open zones when the siren ends or when the confirmation timer expires.
disable - The system will not report a confirmed alarm.
- The system will report a confirmed alarm.
08:ENTRY DELAY 1
09:ENTRY DELAY 2
Two different entry delays allow the user to enter the protected site (while the system is in the
armed state) via 2 specific doors and routes without causing an alarm.
Following entry, the user must disarm the control panel before the entry delay expires. Slow-
rate warning beeps start sounding once the door is opened, until the last 10 seconds of the
delay, during which the beeping rate increases. Locations No. 1 (entry delay 1) and 2 (entry
delay 2) allow you to program the length of these delays.
Options: 10/15/30(ENTRY DELAY 1 default)/45/60(ENTRY DELAY 2 default) seconds;
3/4 minutes
10:ABORT TIME
The PowerMaster 360 can be configured to provide a delay before reporting an alarm to the
Monitoring Station (not applicable to alarms from FIRE, 24H SILENT and EMERGENCY
zones). During this delay period, the siren sounds but the alarm is not reported. If the user
disarms the system within the delay time, the alarm is aborted. You can activate the feature
and select the "Abort Time" interval.
Options: in 00 (default in USA)/15/30 (default)/45/60 seconds; in 2/3/4 minutes
11:CANCEL ALARM
The PowerMaster 360 can be configured to provide a ”Cancel Alarm” time window that starts
upon reporting an alarm to the Monitoring Station. If the user disarms the system within that
"cancel alarm" time, a “cancel alarm” message is sent to the Monitoring Station indicating that
the alarm was canceled by the user.
Options: not active (default in USA); in 1/5 (default)/15/60 minute(s) and in 4 hours.
Enter the "03:DD243 SETUP" menu to configure its settings.
Option Configuration Instructions
01:DISARM OPTION
Define when it is possible to disarm the system:
entry/wl+awy kp – By the control panel when the system is armed AWAY. By keyfob or KP-
160 PG2 during entry delay only.
entry/all devs - During entry delay, when the system is armed AWAY, by all devices. When not
in entry delay by keyfob or KP-160 PG2 only.
entry/DD devs (default) - During entry delay, when the system is armed AWAY, by using the
keyfob or KP-160 PG2. Keypads cannot disarm at all.
– At any time and by all devices.