EasyManua.ls Logo

WAGO 750-882 - Interface Group; Table 478: MIB II - Interface Group

WAGO 750-882
450 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WAGO-I/O-SYSTEM 750 Appendix 413
750-882 Media Redundancy ETHERNET Controller
Manual
1.5.0
16.1.2 Interface Group
The interface group contains information and statistics about the device interface.
A device interface describes the Ethernet interface of a coupler/controller and
provides status information on the physical Ethernet ports as well as on the
internal loopback interface.
Table 478: MIB II Interface Group
Identifier
Entry
Access
Description
1.3.6.1.2.1.2.1
ifNumber
R
Number of network interfaces in this system
1.3.6.1.2.1.2.2
ifTable
-
List of network interfaces
1.3.6.1.2.1.2.2.1
ifEntry
-
Network interface entry
1.3.6.1.2.1.2.2.1.1
ifIndex
R
This entry contains a unique value for each
interface
1.3.6.1.2.1.2.2.1.2
ifDescr
R
This entry contains the name of the
manufacturer, the product name, and the
version of the hardware interface:
e.g., "WAGO Kontakttechnik GmbH 750-841:
Rev 1.0"
1.3.6.1.2.1.2.2.1.3
ifType
R
This entry describes the type of interface.
ETHERNET CSMA/CD = 6
Software Loopback = 24
1.3.6.1.2.1.2.2.1.4
ifMtu
R
This entry specifies the largest transfer unit;
i.e., the maximum telegram length that can be
transferred via this interface.
1.3.6.1.2.1.2.2.1.5
ifSpeed
R
This entry indicates the interface speed in bits
per second.
1.3.6.1.2.1.2.2.1.6
ifPhysAddress
R
This entry indicates the physical address of
the interface. For example, for Ethernet, this
entry contains a MAC ID.
1.3.6.1.2.1.2.2.1.7
ifAdmin-Status
R/W
This entry specifies the desired state of the
interfaces. Possible values are:
up(1):
Ready for operation for
transmission and reception
down(2):
Interface is switched off
testing(3):
Interface is in test mode
1.3.6.1.2.1.2.2.1.8.
ifOperStatus
R
This entry indicates the current operational
state of the interface.
1.3.6.1.2.1.2.2.1.9.
ifLastChange
R
This entry indicates the value of the
sysUpTime when the state was last changed.
1.3.6.1.2.1.2.2.1.10
ifInOctets
R
This entry gives the total number of bytes
received via interface.
1.3.6.1.2.1.2.2.1.11
ifInUcastPkts
R
This entry indicates the number of received
unicast packets delivered to a higher layer.
1.3.6.1.2.1.2.2.1.12
ifInNUcastPkts
R
This entry indicates the number of received
broad and multicast packets delivered to a
higher layer.
1.3.6.1.2.1.2.2.1.13
ifInDiscards
R
This entry indicates the number of packets
that were discarded even though no errors
had been detected.
1.3.6.1.2.1.2.2.1.14
ifInErrors
R
This entry indicates the number of received
packets that contained errors preventing them
from being deliverable to a higher layer.

Table of Contents