1
QUICK REFERENCE OF PARAMETERS AND FAULTS
Param. Description Adjustable range Factory
setting
Page
P0170 Maximum reverse torque current 0 to 250 % 105 % 5-27
P0171 Maximum current of forward torque 0 to 250 % 105 % 5-27
P0175 Flux regulator proportional gain on the
motor
0.0 to 999.9 50.0 5-28
P0176
(3)
Integration constant of the flux regulator
on the motor
1 to 9999 900 5-28
P0178 Rated flux on the motor 0 to 120 % 100 % 5-28
P0179 Maximum flux on the motor 0 to 200 % 120 % 5-28
P0180 Starting point of the field weakening 0 to 120 % 85 % 5-28
P0181
(1)
Magnetization mode 0 = General enable
1 = Start/Stop
0 5-29
P0200 Password 0 = Inactive
1 = Active
1 5-29
P0201 Language selection 0 = Português
1 = English
2 = Español
3 = Deutsch
4 = Français
0 5-29
P0202
(2)(7)
Control Type 0 = V/F 60 Hz
1 = V/F 50 Hz
2 = Adjustable V/F (refer to P0142 to P0146)
3 = Sensorless Vector
4 = Vector with Encoder
0 5-30
P0203
(1)
Special function selection 0 = None
1 = PID regulator
0 5-31
P0204
(1)
Load/Save Parameters 0 = Not Used
1 = Not Used
2 = Not Used
3 = Reset P0043: It resets the enabled time counter.
4 = Reset P0044: It resets the MWh counter.
5 = Load WEG 60 Hz: It reset all the parameters to the
60 Hz factory default values.
0 5-32
P0206 Auto-reset time after fault 0 to 255 s 0 s 5-32
P0208
(2)
Reference scale factor 1 to 18000 1800 5-32
P0209
(1)
Motor phase loss detection 0 = Inactive
1 = Active
0 5-33
P0211 Disable by zero speed (Stop Logic) 0 = Inactive
1 = Active
1 5-34
P0212 Condition for disabable output by zero
speed
0 = P0001 (N*) > P0291 or P0002 (N) > P0291
1 = P0001 (N*) > 0
0 5-34
P0213 Time delay for zero speed disable 0 to 999 s 0 s 5-34
P0214
(6)(7)
Line phase loss detection 0 = Inactive
1 = Active
0 5-34