EasyManua.ls Logo

Woodward GCP-30 Series - Measuring Inputs; Voltage; Figure 5-2: Measuring Inputs - Voltage - Generator; Table 5-3: Terminal Assignment - Generator Voltage Measuring

Woodward GCP-30 Series
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual 37364A GCP-30 Packages - Genset Control
Measuring Inputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Voltage
Generator
L1
L2
L3
N
Generator voltage
MCB GCB
0
N
20 21 22
L3
L2
L1
G
Figure 5-2: Measuring inputs - Voltage - Generator
Terminal Measurement Description A
max
20
400 Vac or
../100 Vac
Generator voltage L1 2.5 mm²
21 Generator voltage L2 2.5 mm²
22 Generator voltage L3 2.5 mm²
0 Neutral point of the 3-phase wye system/transformer 2.5 mm²
Table 5-3: Terminal assignment - generator voltage measuring
NOTE
A GCP-30 controller with 400V PT inputs and potential transformers with 100V secondary outputs must
be used for 480V delta applications. The GCP-30 will not properly protect the generator or system from
overvoltage fault conditions if a GCP-30 with 100V PT inputs is used with 100V potential transformers
or a 400V PT input unit is directly connected to a 480V system. The 100V model inputs are limited to
measuring voltage up to 125V and an overvoltage fault would exceed this range. The 400V model of the
GCP-30 is also unable to monitor for overvoltage faults if potential transformers are not utilized due to
the overvoltage fault exceeding the voltage monitoring range of maximum 500V as well.
NOTE
If a three-wire system is connected, terminal 0 must remain disconnected. If terminal 0 is connected,
the control may monitor a voltage that exceeds the permissible limits.
© Woodward Page 25/46

Table of Contents

Other manuals for Woodward GCP-30 Series

Related product manuals