Manual 37364A GCP-30 Packages - Genset Control
- Setting: ANALOG or PWM (Analog controller) - Frequency-/Power controller
Page 38/46 © Woodward
GND
Speed / power
controller
8 109
GND
PWM
Speed
Governor
GND
PWM
PWM
Speed / power
controller
8 109
A
Voltage
Speed
Governor
A
U
GND
Speed / power
controller
8
A
I
109
GND
Current
Speed
Governor
A
I
GND
N/C
V
Figure 5-19: Analog controller output n/f/P - Wiring and external jumper setting
Type Terminal Description A
max
I
Current
8 I
A
Speed controller /
Frequency controller /
Real power controller
2.5 mm²
9 2.5 mm²
10 GND 2.5 mm²
V
Voltage
8 2.5 mm²
9 V
A
2.5 mm²
10 GND 2.5 mm²
PWM
8 2.5 mm²
9 PWM 2.5 mm²
10 GND 2.5 mm²
Table 5-21: Controller outputs - analog or PWM
- Setting: ANALOG (Analog controller) - Voltage-/Reactive power controller
Voltage / re-active
power controller
11
A
I
1312
GND
Current
AVR
A
I
GND
N/C
Voltage / re-active
power controller
11 1312
A
Voltage
A
U
GND
GND
AVR
V
Figure 5-20: Analog controller output V/Q - Wiring and jumper setting
Type Terminal Description A
max
I
Current
11 I
A
Voltage controller / Reactive power controller
2.5 mm²
12 2.5 mm²
13 GND 2.5 mm²
V
Voltage
11 2.5 mm²
12 V
A
2.5 mm²
13 GND 2.5 mm²
Table 5-22: Controller outputs - analog