Manual 37364A GCP-30 Packages - Genset Control
Relay Outputs
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Controller Outputs
Enable GCB
max. 250 V AC
Command: close GCB
Command: close MCB
Command: open MCB
GCB
MCB
MCB
GCB
4142 141740 39 16 15
Figure 5-14: Relay outputs - Controller outputs - CB activation
Make cont.
Description A
max
14/15 Command: close GCB 2.5 mm²
16/17 [GCP-32] Command: close MCB; [GCP-31] not connected 2.5 mm²
39/40 [GCP-32] Command: open MCB; [GCP-31] Comm.: open ext. CB 2.5 mm²
41/42 Command: open GCB 2.5 mm²
Table 5-16: Relay outputs - terminal assignment
Relay Manager
AB
Relay output
external device
max. 250 V AC
Figure 5-15: Relay outputs - Relay manager
Make cont.
Description A
max
18/19 Ready for operation 2.5 mm²
43/44 Fuel solenoid relay/gas valve 2.5 mm²
45/46 Starter 2.5 mm²
74/75 Relay [R1] (Relay manager) 2.5 mm²
76/77 Relay [R2] (Relay manager) 2.5 mm²
78/79 Relay [R3] (Relay manager) 2.5 mm²
80/81 Relay [R4] (Relay manager) 2.5 mm²
82/83 Relay [R5] (Relay manager) 2.5 mm²
37/38 Relay [R6] (Relay manager; pre-assigned: Preheat/Ignition ON) 2.5 mm²
47/48 Relay [R7] (Relay manager; pre-assigned: Centralized alarm horn) 2.5 mm²
Table 5-17: Relay manager - terminal assignment
© Woodward Page 35/46