EasyManua.ls Logo

Worcester 25/32 - Boiler Location & Clearances

Worcester 25/32
77 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PRE -
INSTALLATION
BOILER LOCATION &
C
LEARANCES
This boiler is only suitable for installing
internally within a property at a suitable
location onto a fixed rigid surface of the same
size as the boiler and capable of supporting
the boiler weight.
The boiler must be installed on a flat level
surface to ensure condensate does not enter
the primary heat exchanger.
The boiler is not suitable for external
installation unless a suitable enclosure is
provided.
Roof space installations must fully conform to
BS 5410 part 1 section 4.6.9.
Open flue model (CF):
In order to ensure clean and efficient
combustion an adequate supply of air must
be delivered to the combustion chamber.
To provide sufficient air a suitable inlet must
be provided into the room or space in which
the boiler is situated.
An air brick or other form of continuous air
supply may have to be built into the installation
in order to ensure an adequate supply of air.
If the appliance is to be installed in a confined
space or compartment two air vents are
required, one at high level and one at low level.
The minimum free area of each vent is
shown opposite and depends whether the
air is taken from another room or from
outside the building.
Where the air is taken from another room that
room must contain an air inlet as described
above.
Room sealed balanced flue model (
R
S):
The appliance does not require a separate vent
for combustion air.
Installation in cupboards or compartments
require permanent vents for cooling purposes
,
one at high level and one at low level
, either
direct to outside air or to a room.
B
oth vents must pass to the s
ame room or be
on the s
ame wall to the outside air.
The minimum air vent free area is given in the
table opposite.
a: INSTALLATION CLEARANCES:
Diagram (
a
) shows the minimum space
recommended to inst
all the boiler only
.
b: S
E
R
VICE CLEARANCES:
Diagram (b) shows the minimum space
required to service the boiler only.
**T
he appliance is suit
able for an under
worktop inst
allation providing that the worktop
above the boiler (min 10mm clearance) is
removable for maintenance and the front of the
boiler is not enclosed.
* Remove the flue 'knock-out' panel sections if
this clearance is less than 7
5mm
.
600mm
300mm
1
00mm
1
00mm
5
70mm
1200mm
1155mm
a: R
ECOMMENDED
I
NSTALLATION CLEARANCES
b: SERVICE CLEARANCES
600mm
300mm**
5mm*
5mm*
380mm
1200mm
1155mm
MINIMUM AIR VENT AREA (cm
2
) FOR APPLIANCES INSTALLED IN A COMPARTMENT:
1
Internal air to and from a space/room inside the building
.
2
Ex
ternal air to and from directly outside the building
.
Conventional flue:
Internal
1
ventilation
High Low
Model Level Level
1
2/
1
8 1
43 2
1
4
18/25 220 330
25/32 275 413
External
2
ventilation
High Low
Level Level
72 143
110 220
138 275
Room Sealed flue:
Internal
1
ventilation
High Low
Model Level Level
12/18 143 143
18/25 220 220
25/32 275 275
Ex
ternal
2
ventilation
High Low
Level Level
72 72
1
1
0 110
1
38 138
12/18
CF minimum air inlet sizes
7
2
1
10
138
18/25 25/32
Output
Size cm
2
BOILER LOCATION & CLEARANCES
I
NSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR CAMRAY KITCHEN 12/18-18/25-25/32
8 716 113 000a (01/07)
13

Related product manuals