EasyManua.ls Logo

Worcester 25/32 - Flue Terminal Positions

Worcester 25/32
77 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Minimum dimensions of flue terminal positions for oil-fired appliances:
TERMINAL POSITION CF RS(H) RS(V)
A
1 2
Directly below an opening, air brick, opening windows, etc N/A 600mm N/A
B
1 2
Horizontally to an opening, air brick, opening window, etc N/A 600mm N/A
C Below a plastic/painted gutter, drainage pipe or eaves if N/A 75mm N/A
combustible material protected
D
3
Below a plastic/painted gutter, drainage pipe or eaves without N/A 600mm N/A
protection to combustible material
E From vertical sanitary pipework N/A 300mm N/A
F From an external or internal corner or from a surface or boundry N/A 300mm N/A
alongside the terminal
G Above ground or balcony level N/A 300mm* N/A
H From a surface or boundary facing the terminal N/A 600mm** N/A
I From a terminal facing the terminal — 1200**mm
J Vertically from a terminal on the same wall N/A 1500mm N/A
K Horizontally from a terminal on the same wall — 750mm —
L Above the point of highest intersection with the roof 600mm 600mm
M From a vertical structure on the side of the terminal 750mm — 750mm
N Above a vertical structure less than 750mm from the side of the terminal 600mm 600mm
O From a ridge terminal to a vertical structure on the roof 1500mm — N/A
— Not applicable
N/A Not allowed
CF Conventional flue
RS(H) Room Sealed Horizontal flue
RS(V) Room Sealed Vertical flue
1 An opening means an openable
element, such as an openable
window, or a permanent opening
such as a permanently open air vent
.
2 Notwithstanding the dimensions
above, a terminal should be at least
300mm from combustible material,
e.g. a window frame.
3 A way of providing protection of
combustible material w
ould be to fit
a heat shield at least 750mm wide.
FLUE TERMINAL POSITIONS
I
NSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR CAMRAY KITCHEN 12/18-18/25-25/32
8 716 113 000a (01/07)
15
PRE -
INSTALLATION
F
LUE TERMINAL POSITIONS
The flue must be fitted and terminated in
accordance with the recommendations of
BS 5410.
Flue terminals must be positioned to avoid
combustion products entering into buildings.
The flue must not cause an obstruction.
Discharge from the flue outlet must not be a
nuisance.
Flue gases have a tendency to plume and in
certain weather conditions a white plume of
condensation will be discharged from the flue
outlet which could be regarded as a
nuisance, for example, near security lighting.
There should be no restriction preventing the
clearance of combustion products from the
terminal.
The air inlet/outlet duct and the terminal of
the boiler must not be closer than 25mm to
any combustible material. Detailed
recommendations on protection of
combustible materials are given in BS 5410:1
A protective terminal guard must be fitted if
the terminal is 2m or less above a surface
where people have access.
The guard must be spaced equally (minimum
50mm) around the flue and fixed to the wall
with plated screws
.
Stainless steet terminal guard:
Part No. 7 716 190 050.
The following additional guidelines (from part
L Exceptions Guidance Document) are
recommended when determining the flue
outlet position:
• Avoid disc
harging flue gases into car ports
or narrow pass
ageways
.
• *Minimum distance of the flue terminal from
above ground is 2
1
00mm where directed to a
public footpath, private access route or a
frequently used area and 2500mm from a
car parking area
.
• **Minimum distance of the flue terminal to a
facing wall, fence, building or property
boundar
y is 2500mm.
O
N
boundary
F
I
H
B
A
G
E
L
C, D
M
F
F
J
K
boundary

Related product manuals