10 Appendix
10.1 Fault Codes
More detailed fault finding procedures are described in the Service Booklet for the Engineer number 7 181 465 347.
Display
code
Description Remedy
A1 pump has run dry Check system pressure, add water and bleed system
as necessary
A7 Hot water NTC sensor defective. Check hot water NTC sensor and connecting lead for
circuit breaks/short circuits.
A8 Break in communication Check connecting lead to TR2
b1 Keyed plug not detected. Insert keyed plug correctly, test and replace if neces-
sary.
C1 Fan speed too low. Check fan lead and connector, and fan; replace as
necessary.
d3 Jumper 8-9 not detected. Connector not connected, link missing, underfloor
heating limiter tripped.
E2 CH flow NTC sensor defective Check CH flow NTC sensor and connecting lead.
E9 Safety temp. limiter in CH flow has tripped. Check system pressure, check safety temp. limiters,
check pump operation, check fuse on pcb, bleed
appliance.
EA Flame not detected. Is gas cock turned on? Check gas supply pressure,
power supply, igniter electrode and lead, ionisation
sensing electrode and lead, flue duct and CO2 level.
F0 Internal error. Check electrical connector contacts, programmer
interface module ignition leads and bus module are
not loose; replace pcb or bus module if necessary.
F7 Flame detected even though appliance switched off. Check electrode assembly, dry pcb. Flue clear?
FA Flame detected after gas shut off. Check gas valve and wiring to gas valve. Clean con-
densation trap and check electrode assembly. Flue
clear?
FC Textdisplay not detected. Check connecting lead between Textdsiplay and
Heatronic , replace Textdisplay if necessary
Fd Reset button pressed by mistake. Press reset button again
P1, P2,
P3, P1...
Please wait, initialisation in progress. 24 V fuse blown. Replace fuse.
Table 18

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Worcester GREENSTAR HE combi Series and is the answer not in the manual?

Worcester GREENSTAR HE combi Series Specifications

General IconGeneral
BrandWorcester
ModelGREENSTAR HE combi Series
CategoryBoiler
LanguageEnglish

Related product manuals