EasyManuals Logo

Worcester GREENSTAR HE combi Series User Manual

Worcester GREENSTAR HE combi Series
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #89 background imageLoading...
Page #89 background image
6 720 610 597 GB (03.02)
Installation
17
3.9 Flue Systems
The only flue systems that may be used are those sup-
plied by Worcester Heat Systems.
The flue system must be installed in accordance with
the requirements of BS5440:1.
Standard 100 mm flue system
The standard concentric flue system provides for a hor-
izontal length of upto 4 m. Full instructions for fitting this
flue are in Subsection 3.9.2 “Installation of the flue”.
Alternative 125 mm diameter flue systems
Installation instructions for the alternative flue systems
are sent with the appropriate flue kit.
Systems are available to give a maximum horizontal
length of 13 m (ZWBR 7-30) and 10 m (ZWBR 11-35).
A vertical flue system upto a height of 15 m (ZWBR 7-
30) and 12 m (ZWBR 11-35) is available.
45° and 90° flue bends can be used with a correspond-
ing reduction in flue length of 2 m for each 90° bend
and 1 m for each 45° bend used.
IMPORTANT: Any horizontal flue system fitted to a
condensing boiler must incline towards the appliance at
an angle of 3 % (30 mm per metre length) to prevent
condensate dripping from the flue terminal. This
means that the clearance above the appliance
must be increased to match the duct length.
Refer to fig. 1 on page 5.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Worcester GREENSTAR HE combi Series and is the answer not in the manual?

Worcester GREENSTAR HE combi Series Specifications

General IconGeneral
BrandWorcester
ModelGREENSTAR HE combi Series
CategoryBoiler
LanguageEnglish

Related product manuals