self-checking
0
E-152
Motor lack of
W phase
UVW phase open
circuit when
self-checking
Check power cable U/V/W
connection
16
0
E-160
Motor output
power overload
Motor output power
over the rated power
1. Change larger power
motor
2. Check the motor shaft
wiring
1
E-161
The heating
power overload
Motor overheating
1 P0-33 confirm motor
code
2. check the motor shaft
connection
3. change larger power
motor
4
E-164
The bus
capacitor
overload
Power supply not
stable, motor load too
large, cause the bus
capacitor charge
frequently
1. use 3 phase 220V power
supply for 220V drive
2. change larger power
motor
5
E-165
Prevent from
blocking alarm
When the blocking time
reached P0-74 (S) and
motor speed lower
than(1rpm), current
motor output torque
larger than P3-28,
P3-29, it will alarm
1. monitor U0-02 motor
torque, check if P3-28,
P3-29 torque setting is
suitable
2. check external
mechanical structure and
installation
6
E-166
Motor
temperature too
high
11KW and 15KW large
power motor encoder
cover is installed
thermistor, will alarm
1. check if the machine has
blocked.
2. if the motor is running
over speed at high torque