EasyManua.ls Logo

Xylem Aquavar - Wire Sizing Charts

Xylem Aquavar
172 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.4 Wire sizing charts
VFD input wire sizing
Maximum allowable conductor length (45°C Ambient, 5% drop)
Line
power
supply
Controller ratings Conductor size for 75°C rated wire (lengths in bold require 90°C rated wire)
Freque
ncy
conver
ter
HP
rating
Input
current
Wires/
phases
3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500
3x460
V AC
1500 150 183 2 717 904 1141 1439
2000 250 291 2 905 1143 1439 1699 2040
2500 300 438 2 1204 1421 1706
3000 350 427 2 1158 1390
4000 450 531 4 992 1252 1577 1862 2236 2613 2988 3718
4500 500 580 4 908 1146 1444 1705 2047 2393 2736 3404
5000 550 667 4 997 1256 1483 1780 2080 2379 2960
6000 600 718 4 1167 1377 1654 1933 2210 2749
3x575
V AC
2000 200 189 2 695 875 1104 1393
2500 250 234 2 892 1125 1421 1790 2113 2537
3000 300 286 2 921 1163 1464 1729 2076
3500 350 339 2 1235 1459 1751
4000 400 390 2 1268 1522
4500 450 434 4 962 1214 1532 1930 2279 2736 3197 3656 4549
5000 500 482 4 866 1093 1380 1738 2052 2463 2879 3292 4096
6000 600 549 4 959 1211 1526 1801 2163 2528 2890 3596
VFD output wire sizing
Maximum allowable conductor length (45°C Ambient, 5% drop)
Line
power
supply
Controller ratings Conductor size for 75°C rated wire (lengths in bold require 90°C rated wire)
Freque
ncy
conver
ter
HP
rating
Input
current
Wires/
phases
3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500
3x460
V AC
1500 150 190 2 691 870 1099 1386
2000 200 240 2 870 1097
2500 250 302 2 872 1101 1387 1637 1966
3000 300 361 2 1160 1370 1644
3500 350 443 2 1116 1340
4500 450 540 4 975 1231 1551 1831 2199 2570 2939 3656
5000 500 590 4 893 1127 1420 1676 2012 2352 2690 3346
5500 550 678 4 981 1235 1459 1751 2047 2340 2912
6000 600 730 4 1147 1355 1626 1901 2174 2704
9 Technical Specification
162 Aquavar
®
Intelligent Pump Controller - 150 HP to 600 HP INSTRUCTION MANUAL

Table of Contents