EasyManua.ls Logo

Xylem Aquavar - Page 65

Xylem Aquavar
172 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
c. Insert the cable in the adjacent circular hole.
d. Remove the screwdriver. The wire is now mounted to the terminal.
2. To remove the wire from the terminal:
a. Insert a screwdriver (2.5–3.5 mm) in the rectangular hole and push it down.
b. Pull out the cable.
9 - 10 mm
(0.37 in)
Figure 72: Connecting and disconnecting control wiring
Analog input configuration
There are two analog input switches, A53 is fixed to Current (4-20mA) only; whereas, the
A54 input switch can be selected as Voltage (0-10V) or Current (4-20mA).
Switch A53 is fixed to current type and not configurable.
Switch A54 is used to configure analog input 54.
If the analog input 54 is used, the analog input configuration switch A54 must be set
properly.
Remove power from the controller before changing the analog input configuration
switches.
Remove the local control panel.
To configure the analog input 54 as a voltage input, set the configuration switch A54 to
U (set to the left position).
Set the configuration switch A54 to I (set to the right position) to enable the input as a
current input.
Transducer voltage or current type of switch A54 can be verified at parameter [16-63]
Terminal 54 Switch Setting. NOTE: [16-61] Terminal 53 Switch Setting always displays
current type.
5 Electrical Installation
Aquavar
®
Intelligent Pump Controller - 150 HP to 600 HP INSTRUCTION MANUAL 63

Table of Contents

Related product manuals