EasyManua.ls Logo

Xylem LOWARA e-SV Series - Maximum number of starts per hour; Protection class

Xylem LOWARA e-SV Series
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
en Translation of the Original Instructions
e-SV series Additional Installation, Operation and Maintenance Instructions 45
Note for the pump unit: the maximum ambient temperature is 50°C (122°F), unless otherwise
stated on the data plate of the motor and/or frequency converter, if present.
Note:
P1max + Pmax ≤ PN
Data
Description
P1max
Maximum input pressure
Pmax
Maximum pressure generated by the unit
PN
Maximum operating pressure
8.5 Maximum number of starts per hour
Motor power, kW (hp)
Starts / h
0.25 – 3 (0.33 4)
60
4 – 7.50 (5.4 – 10)
40
11 15 (14.8 – 20.1)
30
18.5 22 (24.8 29.5)
24
30 37 (40.2 – 49.6)
16
45 75 (60.3 – 100)
8
90 160 (120 215)
4
NOTICE:
If a motor other than the one supplied with the pump unit is used, check the maximum number
of starts shown in the motor manual.
8.6 Protection class
IP 55.
ESV_M0014_A_sc