EasyManua.ls Logo

Xylem LOWARA e-SVE - Parameters Menu Visualization

Xylem LOWARA e-SVE
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
en Original instructions
34
-0-
Lock
To lock press + for 3 seconds; the lock will be confirmed by the temporary appearance
of
-0-
It appears if a button is pressed (with the exception of ) after a locking procedure had been
completed.
Note: the function connected with START/STOP is always disabled. At startup the buttons
are locked, if they were locked at the previous switch off
Default: unlocked
( )
Unblock
To unlock press + , for three seconds; the unlock will be confirmed by the temporary
appearance of ( )
Note: At startup the buttons are unlocked, if they were unlocked at the previous switch off
Default: unlocked
6.4.2 Parameters menu visualization
The parameter menu gives the possibility to:
select all the parameters (see Par. 6.5)
access Parameter View / Editing (see Par. 6.2).
Parameter
Description
Power on
If after switching ON, parameter Menu View is accessed with P23 = ON, P20 flashes
P20
P20
.
Enter the password to display and change the parameters.
Password timeout
If with P23 = ON no button is pressed for over 10 minutes from the last parameter Menu
View, both the view and the editing of the parameters are disabled.
Enter the password again to display and change the parameters.
Parameters Menu
With P23 = OFF, or after entering the password (P20), it is possible to both display and edit
the parameters. When accessing the Parameter Menu, the display shows:
P01
P01
P02
P02
...
P69
P69
The flashing parameter, indicating the selection possibility.
Parameters
Editing/Visualization
The value of a parameter may be changed using the buttons, or the Modbus and BACnet
communication protocols.
When returning to the Parameter Menu, the displayed parameter index is increased
automatically. For further information see Par. 6.5.
Example A (P20) from 000 to 066:
P20
P20
000
000
… until
066
066
sets the
desired value
P21
P21
Example 2 (P26) from 360 to 300:
P26
P26
360
360
… until
300
300
sets the
desired value
P26
P26
.

Table of Contents

Other manuals for Xylem LOWARA e-SVE

Related product manuals