EasyManua.ls Logo

Xylem LOWARA e-SVE - Technical References; Example: ACT Control Mode with Analog Input

Xylem LOWARA e-SVE
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
en Original instructions
42
6.6 Technical references
6.6.1
Example: ACT control mode with analog input
The diagram of the ACT control mode is shown in the figure.
No.
Description
1
ZERO point (0Vdc - 4mA) = minimum analog signal value
2
Adjustment start point
3
Standby point (SBY) = 1/3 of the hysteresis zone
4
ON point (ON) = 2/3 of the hysteresis zone
5
MAX point (10Vdc - 2mA) = maximum analog signal value
6
Motor minimum speed (Parameter P27)
7
Motor maximum speed (Parameter P26)
8
Adjustment zone
3 - 4 - 2
Minimum speed operation zone (Parameter P27)
1 to 2
Hysteresis zone
1 - 3 - 4
Standby zone
For further information on the control mode and the ACT regulation parameters, see Par. 6.5.3.
and 6.5.5
Examples:
Calculation of the adjustment start point
for P40 = ISP (4-20 mA analog signal)
P27 = 900
P26 = 3600
Calculation of the adjustment start point value = (maximum value
- zero point) x (P27/P26) + zero point = (20-4) x (900/3600) + 4 = 8
mA
Calculation of the adjustment start point
for P40 = VSP (0-10 Vdc analog signal)
P27 = 900
P26 = 3600
Calculation of the adjustment start point value =
(maximum value - zero point) x (P27/P26) + zero point = (10-0) x
(900/3600) + 0 = 2.5 V

Table of Contents

Other manuals for Xylem LOWARA e-SVE

Related product manuals