No. Parameter Name Setting Range Default
E1-06 Base Frequency 0.0 to 400.0 Hz
60 Hz
<2>
E1-07 Middle Output Frequency 0.0 to 400.0 Hz
3.0 Hz
<2>
E1-08 Middle Output Frequency Voltage
0.0 to 255.0 V
<1>
16.0 V
E1-09 Minimum Output Frequency 0.0 to 400.0 Hz
1.5 Hz
<2>
E1-10 Minimum Output Frequency Voltage
0.0 to 255.0 V
<1>
12.0 V
<1> Values shown here are for 200 V class drives; double the values for 400 V class drives.
<2>
The default value is for the following localized drives: Japan (Model code: CIMR-JAoA) and Asia (Model
code: CIMR-JToA) .Refer to China Localized Drive Default Values on page 246 for the default values of
China localized (Model code: CIMR-JBoA) drives.
E1-05
E1-08
E1-10
E1-09 E1-07 E1-06 E1-04
Output Voltage (V)
Frequency (Hz)
Figure 4.16 V/f Pattern
Note: 1. The following condition must be true when setting up the V/f pattern: E1-09 ≤ E1-07 < E1-06 ≤
E1-04
2. To make the V/f pattern
a straight line set E1-09 = E1-07. In this case the E1-08 setting is disregarded.
3. E1-03 is unaffected when the drive is initialized using parameter A1-03, but the settings for E1-04
through E1-10 are returned to their default values.
u
Motor Parameters: E2-01 to E2-03
n
Setting Motor Parameters
The following table provides instructions on how
to set motor parameters. Refer to the motor
data sheet for the correct motor data.
4.5 Basic Operation
110
YASKAWA ELECTRIC TOEP C710606 25D YASKAWA AC Drive J1000 Installation & Start-Up Manual