5.8 Troubleshooting without Fault Display
This section describes troubleshooting problems that do not trip an alarm or fault.
u
Cannot Change Parameter Settings
Cause Possible Solutions
The drive is running the motor (i.e., the
Run command is present).
Stop the drive and switch over to the Programming Mode.
Most parameters cannot be edited during run.
The Access Level is set to restrict access
to parameter settings.
Set the Access Level to allow parameters to be edited (A1-01 = 2).
The operator is not in the Parameter Setup
Mode (the LED screen will display
“PAr”).
See what mode the LED parameter is current set for.
Parameters
cannot
be
edited
when
in
the
Setup Mode (“STUP”). Switch
modes so that “PAr” appears on the screen.
The wrong password was entered.
If
the password entered to A1-04 does not match the password saved to
A1-05, then drive settings cannot be changed.
Reset the password.
If you cannot remember the password:
Display parameter A1-04. Press the
STOP
button while pressing
at the same time. Parameter A1-05 will appear.
Set a new password to parameter A1-05.
Undervoltage was detected.
Check the drive input power voltage by looking at the DC bus voltage
(U1-07).
Check all main circuit wiring.