EasyManua.ls Logo

YASKAWA CIMR-JB Series - Page 172

YASKAWA CIMR-JB Series
287 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Inspection
Category
Inspection Points Corrective Action Checked
Cooling Fan Inspect drive cooling fan operation.
Check for clogged or dirty fan.
Check
fan
operation
drive
parameter.
Environment
Verify the drive environment complies
with the specifications listed in the
Installation section of this manual.
Eliminate
the
source
of
contaminants
or correct poor environment.
Load
The drive output current should not be
higher
than
the
motor
or
drive
rating
for
an extended period of time.
Check for excessive load.
Check the motor parameter settings
of the drive.
Power Supply
Voltage
Check main power supply and control
voltages.
Correct the voltage or power supply
to within nameplate specifications.
Verify all main circuit phases.
6.2 Inspection
172
YASKAWA ELECTRIC TOEP C710606 25D YASKAWA AC Drive J1000 Installation & Start-Up Manual

Table of Contents

Related product manuals