B Parameter Table
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 185
■ H2: Multi-Function Digital Outputs
No. Name Description Setting
H2-01
Terminals M1-M2
Function Selection (relay)
Refer to H2 Multi-Function Digital Output Settings on page 185 for a description of
setting values.
Default: 50
Min: 0
Max: 161
H2-02
Terminals M3-M4
Function Selection (relay)
Default: 51
Min: 0
Max: 161
H2-03
Terminals M5-M6
Function Selection (relay)
Default: 6
Min: 0
Max: 161
H2-04
Terminal P1-C1 Function
Selection (photocoupler)
Default: 37
Min: 0
Max: 161
H2-05
Terminal P2-C2 Function
Selection (photocoupler)
Default: F
Min: 0
Max: 161
H2 Multi-Function Digital Output Settings
H2-
Setting
Function Description
0 During Run Closed: An Up/Down command is active or voltage is output.
1 Zero Speed
Open: Output speed is greater than the value of E1-09 (Minimum Output Frequency) or S1-01 (Zero
Speed Level at Stop).
Closed: Output frequency is less than or equal to the value of E1-09 (Minimum Output Frequency) or
S1-01 (Zero Speed Level at Stop).
2 Speed Agree 1 Closed: Output speed equals the speed reference (plus or minus the hysteresis set to L4-02).
3 User-set Speed Agree 1 Closed: Output speed and speed reference equal L4-01 (plus or minus the hysteresis set to L4-02).
4 Speed Detection 1 Closed: Output speed is less than or equal to the value in L4-01 with hysteresis determined by L4-02.
5 Speed Detection 2 Closed: Output speed is greater than or equal to the value in L4-01 with hysteresis determined by L4-02.
6 Drive Ready (READY) Closed: Power up is complete and the drive is ready to accept an Up/Down command.
7 DC Bus Undervoltage Closed: DC bus voltage is below the Uv trip level set in L2-05.
8 During Baseblock (N.O.) Closed: Drive has entered the baseblock state (no output voltage).
9 Speed Reference Source
Open: The speed reference is supplied by an external reference (set in b1-01).
Closed: Digital operator supplies the speed reference.
A Up/Down Command Source
Open: The Up/Down command is supplied by an external reference (set in b1-02).
Closed: Digital operator supplies the Up/Down command.
B Torque Detection 1 Closed: An overtorque or undertorque situation has been detected.
E Fault Closed: Fault occurred. (excluding CPF00 and CPF01)
F Not used (Through Mode) Set this value when the terminal is not used or when using the terminal in the pass-through mode.
10 Minor Fault Closed: An alarm has been triggered, or the IGBTs have reached 90% of their expected life span.
11
Fault Reset Command
Active
Closed: The drive has received a reset command from the multi-function input terminals or from serial
network, or the digital operator’s RESET key has been pressed.
12 Timer Output Closed: Timer output.
13 Speed Agree 2 Closed: When drive output frequency equals the speed reference ±L4-04.
14 User-set Speed Agree 2 Closed: When the drive output speed is equal to the value in L4-03 ±L4-04.
15 Speed Detection 3 Closed: When the drive output speed is less than or equal to the value in L4-03 ±L4-04.
16 Speed Detection 4 Closed: When the output speed is greater than or equal to the value in L4-03 ±L4-04.
18 Torque Detection 2 Closed: Overtorque or undertorque has been detected.
1A During Down Direction Closed: Drive is running in the down direction.
1B During Baseblock 2 (N.C.) Open: Drive has entered the baseblock state (no output voltage).