2.15 Using Message Functions
Using Function Codes
2-377
Ethernet Communications
The following example illustrates how data is written using no-protocol communications. In this example,
1,500 words of data starting from register IW07800 in the local station are written to registers starting at
MW0800000 in the remote station.
PARAM22
Local Station Register
Type
Set the register type (M, G, I, O, or S) of the data to be written that is
stored in the local station.
PARAM24 For system use
Set this parameter to 0 from a user program or by other means in the
first scan after the power is turned ON. Thereafter, do not change the
value of this parameter. This parameter is used by the system.
1. The registers in the remote station are specified by the M Register Writing Range Low parameter in
the MSG-RCVE function.
2. Set the address of the registers to write to within the range specified by the M Register Writing
Range Low and M Register Writing Range High parameters in the MSG-RCVE function. Data will
not be written if an address exceeds the valid setting range.
Continued from previous page.
MSG-SNDE Function Parameter Description
IW07800
MW0800000
MW0000000
12
13
14
10
11
15
16
17
18
19
20
21
22
0000 hex
0000 hex
0000 hex
0001 hex
0000 hex
0000 hex
0000 hex
05DC hex
0000 hex
0000 hex
7800 hex
0000 hex
0002 hex
IW00000
7800 hex
5DC hex(1500)
0001 hex
0000 hex
0000 hex
10
20
21
0000 hex
11
0000 hex
0000 hex
22
23
0000 hex
0000 hex
24
25
0000 hex
0000 hex
26
27
0000 hex
0000 hex
28
29
0000 hex
0000 hex
30
31
0000 hex
0000 hex
32
33
0000 hex
0000 hex
34
35
3500 hex
000C hex
36
37
FFFF hex
000F hex
38
39
0000 hex
0000 hex
40
41
FFFF hex
001F hex
42
43
0000 hex
0000 hex
44
45
7FFF hex
0001 hex
46
47
IW07DDB
MW0801499
MW1048575
C3500 hex(800000)
FFFFF hex(1048575)
MP3000-series Controller (Send: master)
MP3000-series Controller (Receive: slave)
MSG-SNDE Function
Parameter List
Use connection number 1.
I registers
MSG-RCVE Function
Parameter List
Use connection number 1.
M registers
M Writing Range Low
Data size: 1,500 words
M Register Writing
Range High
Data
Local station
data addresses
Data size: 1,500 words
Data
2 = I registers
Example of Addressing and Offset Addressing with No-Protocol Communications