3.3.3 Removable Conduit Panel
All conduit connections must be made in a manner consistent with maintaining the NEMA
rating of the enclosure; failure to do so could result in a loss of warranty coverage.
All conduit entries must pass through the removable conduit panel. All modifications to the removable panel must occur
when the panel is detached from the inverter. This prevents metal shavings and other debris from potentially damaging
the inverter. Remove the 10 screws using a #3 Phillips-head screwdriver. When modifications are complete, replace all
10 screws and torque to 25 in-lbs (2.8 Nm).
All modifications to the conduit panel must be contained within the region shown in Figure 3-9. For inverters paired with
the attachable combiner box, the removable conduit panels for each require a 2” hole to accommodate the provided
conduit and wire assembly. Modify the removable panels so this hole is located as shown in Figure 3-10 for the inverter
and as shown in Figure 3-11 for the attachable combiner.
Figure 3-9 Removable Conduit Panel – Entry Locations